Hagemann Elementary School

Water Testing Results: Hagemann Elementary School

SCI collected 44 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.

The drinking water samples that exceeded the state's new action level are identified below.


Published: April 9, 2024
Updated: Sept. 5, 2024

Sample location

Sample description

Result (ppb)

Remediation

Retest Results (ppb)

Kitchen

Triple Basin Sink, Middle Faucet

17.4

Installed new faucet

4.29

Kitchen

Triple Basin Sink, Right Faucet

10.5

Installed new faucet

10.5

Library Office

Sink

26.6

Installed new faucet

6.04

On a mobile phone? Turn your phone to landscape.

The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.

See testing result report from SCI.

Return to Safe Water at School.

The Mehlville School District strictly prohibits discrimination and harassment against employees, students or others on the basis of race, color, religion, national origin, age, disability, or sex including pregnancy, sexual orientation, and gender identity and other characteristics protected by law. The following individuals have been designated to handle inquiries regarding the non-discrimination policies: contact Adam Smith at 314-467-5006 or [email protected].