SCI collected 60 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples that exceeded the state's new action level are identified below.
Published: April 9, 2024
Updated: February 7, 2025
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
Kitchen |
Double Basin Sink, Right Faucet |
6.42 |
Replaced faucet |
1.77 |
Kitchen |
Combi-Oven |
15.6 |
Installed new filters |
1 |
Kitchen |
Handwashing Sink |
9.03 |
Replaced faucet |
1 |
Kitchen |
Triple Basin Sink, Left Faucet |
9.70 |
Replaced faucet |
<1.0 |
Library Office |
Sink |
12.9 |
Installed new aerator |
1.1 |
Room 24 |
Sink Faucet |
12.5 |
Installed new stem and aerator |
4.68 |
Room 23 |
Water Fountain |
17.6 |
Removed and capped |
N/A |
Room 22 |
Sink Faucet |
24.3 |
Installed new stem and aerator |
4.68 |
Room 22 |
Sink Spray Nozzle |
166 |
Removed and capped |
N/A |
Room 21 |
Sink Faucet |
8.69 |
Replaced faucet |
1.06 |
Room 20 |
Sink Faucet |
14.0 |
Installed new stem and aerator |
4.61 |
Room 19 |
Sink Spray Nozzle |
722 |
Removed and capped |
N/A |
Room 18 |
Sink Faucet |
8.21 |
Replaced faucet |
3.96 |
Room 15A |
Sink Faucet |
13.4 |
Non-potable water sign installed |
N/A |
Room 14 |
Sink Faucet |
8.22 |
Replaced faucet |
2.23 |
Room 13 |
Sink Faucet |
7.04 |
Installed new stem and aerator |
2.92 |
Room 13 |
Sink Spray Nozzle |
13.1 |
Removed and capped |
N/A |
Room 12 |
Sink Faucet |
8.49 |
Replaced faucet |
3.74 |
Room 12 |
Sink Spray Nozzle |
63.1 |
Removed and capped |
N/A |
Room 11 |
Sink Faucet |
8.44 |
Replaced faucet |
3.54 |
Room 10 |
Sink Faucet |
6.71 |
Replaced faucet |
4.06 |
Room 10 |
Sink Spray Nozzle |
23.6 |
Removed and capped |
N/A |
Room 9 |
Sink Faucet |
51.2 |
Replaced faucet |
4.52 |
Room 9 |
Sink Spray Nozzle |
9.69 |
Removed and capped |
N/A |
Room 8 |
Sink Faucet |
10.2 |
Replaced faucet |
1.72 |
Room 6 |
Sink Faucet |
15.8 |
Installed new stem and aerator |
3.03 |