Oakville Middle School
Water Testing Results: Oakville Middle School
SCI collected 35 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples that exceeded the state's new action level are identified below.
Published: April 9, 2024
Updated: February 7, 2025
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
Kitchen |
Triple Basin Sink, Right Faucet |
22.1 |
Installed new faucet |
3.11 |
Room 103 |
Sink 1 |
6.14 |
Installed new aerator |
3.78 |
Hallway by Room 101 |
Water Fountain |
16.7 |
Installed new bubbler |
|
Room 102 |
Sink |
193 |
"Non-potable water" signage installed |
N/A |
Library |
Sink |
34.5 |
Installed new stem and aerator |
5.3 |
Room 113 |
Right Sink |
958 |
"Non-potable water" signage installed |
N/A |
Science Office |
Sink |
20.6 |
"Non-potable water" signage installed |
N/A |
Hallway by Room 201 |
Right Fountain |
7.96 |
Removed and capped |
N/A |
On a mobile phone? Turn your phone to landscape.
Notes: Room 102 Sink was used for hand-washing only. Room 113 Right Sink was used for hand-washing but has been out of order and not in use.
The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.
See testing result report from SCI.
Return to Safe Water at School.