MOSAIC Elementary School
Water Testing Results: MOSAIC Elementary School
SCI collected 28 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples that exceeded the state's new action level are identified below.
Published: April 9, 2024
Updated: December 12, 2024
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
First Floor Room 108 |
Sink |
8.9 |
Installed new faucet |
2.2 |
First Floor Room 109 |
Sink |
6.9 |
Installed new faucet |
2.64 |
Room 215 |
Sink |
8.3 |
Installed new faucet |
4.98 |
Room 217 |
Sink |
8.7 |
Installed new faucet |
4.94 |
Room 218 |
Left Sink |
6.7 |
Installed new faucet |
3.77 |
Room 218 |
Right Sink |
7.9 |
Installed new faucet |
3.72 |
Room 306 |
Sink |
11.3 |
Installed new faucet |
<1 |
Room 304 |
Sink |
21.0 |
Installed new faucet |
<1 |
Room 302 |
Sink |
11.8 |
Installed new faucet |
<1 |
Room 301 |
Sink |
14.9 |
Installed new faucet |
4.65 |
Room 305 |
Sink |
5.3 |
Installed new faucet |
<1 |
On a mobile phone? Turn your phone to landscape.
The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.
See testing result report from SCI.