Forder Elementary School
Water Testing Results: Forder Elementary School
SCI collected 48 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples that exceeded the action level are identified below.
Published: April 9, 2024
Updated: August 12, 2024
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
Room 111 |
Front Wall Left Sink |
5.6 |
Installed new faucet |
2.6 |
Room 111 |
Side Wall Sink |
23.3 |
Installed new faucet |
2.5 |
Kitchen |
Mixer Faucet |
512 |
Removed and capped |
N/A |
Kitchen |
Garbage Disposal Sink |
8.5 |
Installed new aerator |
1 |
Dishwashing Room |
Triple Basin Sink, Middle Sink |
15.3 |
Installed new faucet |
1 |
Room 112 |
Water Fountain |
5.6 |
Installed new bubbler |
1.9 |
Nurse’s Office |
Sink |
9.0 |
Installed new faucet |
2.52 |
On a mobile phone? Turn your phone to landscape.
Note: Room 111 is an art room with sinks primarily used for cleaning. The Kitchen Mixer Faucet was not being used.
The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.
See testing result report from SCI.