Buerkle Middle School
Water Testing Results: Buerkle Middle School
SCI collected 53 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples that exceeded the the state's new action level are identified below.
Published: April 9, 2024
Updated: October 24, 2024
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
Room 104 - Workroom |
Sink |
33.2 |
"Non-potable water" signage installed |
N/A |
Room 104 |
North Sink |
23.6 |
New faucet installed |
4.09 |
Room 104 |
South Sink |
26.0 |
New faucet installed |
3.25 |
Dishwashing Room |
Handwashing Sink |
5.0 |
Installed new aerator |
1 |
On a mobile phone? Turn your phone to landscape.
Note: Room 104 sinks are rarely used.
The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.
See testing result report from SCI.
Return to Safe Water at School.