Blades Elementary School
Water Testing Results: Blades Elementary School
SCI collected 61 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.
The drinking water samples which exceeded the action level are identified below.
Published: April 9, 2024
Updated: October 24, 2024
Sample location |
Sample description |
Result (ppb) |
Remediation |
Retest Results (ppb) |
Kitchen |
Round Sink |
42.3 |
Installed new faucet |
3.35 |
Room 113 |
Water Fountain |
11.7 |
Installed new bubbler |
1 |
Library |
Sink |
10.2 |
Installed new faucet and capped bubbler / "Non-potable water" sign installed |
N/A |
Room 207 |
Water Fountain |
6.04 |
Installed new bubbler |
2.9 |
Room 212 |
Water Fountain |
6.42 |
Installed new bubbler |
1 |
On a mobile phone? Turn your phone to landscape.
Notes: The kitchen round sink is currently not used by school food staff.
The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.
See testing result report from SCI.
Return to Safe Water at School.